Product Details
UPC: 4.71E+12
Brand: CyberPower


About CyberPower 40KVA/40KW Rack UPS



CP 40KVA/40KW Rack UPS



Specifications:




  • Phase: Three Phase


  • Form Factor: Rackmount, Tower


  • UPS Topology: Online Double Conversion


  • Energy Saving Technology: Online ECO Mode Efficiency > 98.9%


  • Normal Mode Efficiency ( % ): 95.8%


  • Battery Mode Efficiency ( % ): 95.5%


  • Active PFC Compatibility: Yes


  • Parallel Expansion (Max. Units): 4


  • Dual Power Inputs: Yes


  • Generator Compatibility: Yes


  • Nominal Input Voltage ( Vac ): Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac


  • Input Voltage Range ( Vac ): Line to Neutral (L-N): 132 ~ 276 Vac, Line to Line (L-L): 228 ~ 478 Vac


  • Input Frequency Range ( Hz ): 40 ~ 70


  • Rated Input Current ( A ): 64.5


  • Input Power Factor: 0.99


  • Overload Protection (Bypass): 125% Load for continuous operation, 150% Load for 10 min, 1000% Load for 5 ms


  • Input Connector Type: Hardwire Terminal Block


  • Capacity (VA): 40000


  • Capacity (Watts): 40000


  • On Battery Waveform: Pure Sine Wave


  • Output Voltage Setting: Configurable


  • Output Frequency Setting: Configurable


  • Rated Output Voltage ( Vac ): Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac


  • Output Voltage Tolerance ( % ): Balance Load: 1 %


  • Output Frequency ( Hz ± % ): 50 ± 0.2, 60 ± 0.166


  • Power Factor: 1


  • ECO Mode Voltage Tolerance: ± 5 %


  • Overload Protection: Internal Current Limiting, Fuse


  • Overload Protection (Line Mode): 102~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load for 200 ms


  • Overload Protection (Battery Mode): 102~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load for 200 ms


  • Crest Factor: 3 : 1


  • Harmonic Distortion (Linear Load): THD 1%


  • Harmonic Distortion (Non-linear Load): THD 3%


  • Internal Bypass: Automatic Bypass


  • Synchronization Window (Nominal) ( Hz ): ± 4


  • Outlet Type: Hardwire Terminal Block x 1


  • Typical Transfer Time ( ms ): 0


  • Maximum Charging Current ( A ): 12


  • Typical Charging Current ( A ): 3.6


  • Compatible Battery Types: VRLA


  • Recharge Power Setting: Configurable


  • Charger Voltage Tolerance ( % ): 1 %


  • Start On Battery: Yes


  • Smart Battery Management (SBM): Yes


  • Compatible Extended Battery Module (EBM): BME480V55ART5U


  • External Battery Quantity: 12V x 40pcs


  • EMI/RFI Filtration: Yes


  • LCD Panel: Yes


  • LCD Types: Color LCD, LCD Touch Panel


  • LCD Orientation: Rotatable LCD Manual


  • LCD Information Display: Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log


  • LCD Setting & Control: Mode Setting, Input & Output, Battery Setting, Communication, Event & Log, Security Setting, Language


  • LED Indicators: Yes


  • Shortcut Button: Alarm On/Off


  • Serial Port: RS232 x 1 + RS485 x 1 + Dry Contact x1


  • Dry Contact (with Relay): Yes


  • Emergency Power Off (EPO) Port: Yes


  • Audible Alarms: Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery


  • Power Management Software: PowerPanel Business (Recommended)


  • SNMP/HTTP Remote Monitoring: Yes - with optional RMCARD205


  • Compatible with Racks (3 Phase): Yes


  • Enclosure Construction: Metal


  • Color: Black


  • Ingress Protection: IP20


  • Rackmount Rail: Yes


  • Dimensions (mm.): 433 x 219 x 730


  • Weight (kg.): 42.8


  • Installed Rack Height ( U ): 5


  • Operating Temperature (°C): 0 ~ 40


  • Operating Relative Humidity (Non-condensing) ( % ): 0 ~ 95


  • Operating Elevation (meters): 0-3,000


  • Storage Temperature (°C): -40 ~ 70


  • Storage Relative Humidity (Non-condensing) ( % ): 0 ~ 95


  • Audible Noise at 1.0M from Surface of Unit: 66dBA(100% load), 56dBA(50% load)



Features:




  • Three-phase Design


  • High Output Power Factor


  • Color LCD Panel


  • Dual Inputs


  • Pure Sine Wave Output


  • Battery Cold Start


  • SNMP/HTTP Remote Management Capability (Optional)


  • Extended Battery Module (EBM)


  • Online (Double Conversion) UPS Topology


  • Rack Modular Design


  • LCD Touch Panel


  • Generator Compatible


  • UPS Parallel Expansion


  • Smart Battery Management (SBM)


  • PowerPanel Management Software



Download Brochure